Xtralis VESDA VLC Aspirating Smoke Detector

Key Features
Absolute smoke detection
Wide sensitivity range
Single pipe inlet
Referencing
VESDAnet communication (VN)
Clean air barrier optics protection
Airflow monitoring
AutoLearn™

Overview

VESDA VLC Aspirating Smoke Detectors have been specifically designed to provide all the benefits of aspirating smoke detection in single environment small areas and where space is limited.

VLC detectors incorporate a modified aspirator design combined with the well-proven VESDA VLP detection technology into a compact enclosure with a simplified display.

There are two main versions of the VLC available: one that interfaces via relays only (RO) and one that interfaces via relays and VESDAnet (VN).

There is also an Apollo XP95 version that is specifically designed to support the Apollo communication protocol. This version also has a loop in/out connection, which negates the need for an additional interface to monitor the fault and fire signal.

The VN version allows several detectors to be linked together on VESDAnet which allows one to act as a reference detector for other VESDA detectors. A Remote Display module is also available for use with the VN version of the VLC, that provides the ability for the current status of the detector to be reported in a convenient location. The Remote Display module has 7 remote relays to support any combination of signalling required by the application.

There are two parts to the VLC: the main enclosure and the front cover.

All the key components of the detector are housed in the main enclosure. All non-serviceable items, such as the main processor board and detector chamber, are mounted away from the general access areas so they are protected during the installation and service process.

The front cover includes a five-LED display with Fire, Pre-alarm/alert, Fault, OK and Rest/Isolate indication and a Reset/Isolate push button (press to reset, press and hold to isolate).

How it Works

A high-efficiency aspirator is used to continually draw air into a central detector unit via a simple pipe network.

The air is passed through a flow sensor before a sample is transferred through a dual-stage dust filter. This filter removes any dust and dirt from the sample before it enters the chamber for detection.

A highly-efficient laser light source and unique sensor configuration are used in the chamber to achieve the optimum response to a broad range of smoke types.

When smoke passes through the detection chamber the VLCs very sensitive sensor circuitry detects light scatter caused by any smoke in the chamber.

All alarms, service and fault events are monitored and logged with time and date stamps, and status reporting can be transmitted via simple relay connections, or across the advanced VEDSnet communications network (VN version only).

Other Features

  • Three Alarm Level
  • Three Programmable Relays
  • Optional remote display and relay capability
  • Simple mounting design
  • Five status LED

Approvals

UL
ULC
FM
CCC
ActivFire
CE
LPCB
VdS
NF
VNIIPO
EN-54-20:
  • Class A (30 holes / 0.05% obs/m)
  • Class B (36 holes / 0.09% obs/m)
  • Class C (40 holes / 0.165% obs/m)
Classification of any configuration is determined using ASPIRE2.

Tech Specs

Input Power

Supply Voltage

18 to 30 VDC

Power Consumption

5.4 W quiescent, 5.9 W with alarm

Current Consumption

225 mA quiescent, 245 mA with alarm

Fuse Rating:

1.6 A

General

Dimensions (W x H x D)

225 mm x 225 mm x 85 mm (8 7/8” x 8 7/8”x 3 3/8”)

Weight

1.9 kg (4.2 lbs.)

Computer design tool

ASPIRE2™

IP Rating

IP 30

Cable Access

4 x 25 mm (1”) cable entries

Cable termination:

Screw Terminal blocks 0.2–2.5 sq mm (30–12 AWG)

Alarm sensitivity range:

0.005% to 20% obs/m (0.0015% to 6.25% obs/ft)

Relays

3 Relays rated 2 A @ 30 VDC Fire (NO) Pre-Alarm (NO) Alert/Fault (Maintenance & Isolate) (NC/NO) Configurable as latching or non-latching

Event Log

Up to 12,000 events stored in FIFO format Smoke level, user actions, alarms and faults with time and date stamp

AutoLearn

Minimum 15 minutes, maximum 15 days. Recommended minimum 14 days. During AutoLearn thresholds are NOT changed from pre-set values.

Configurable General Input (24 VDC):

Standby, Mains OK or Reset/Isolate

Threshold Setting Range

Alert

0.005%–1.990% obs/m (0.0015%–0.6218% obs/ft)

Pre-Alarm

0.010%–1.995% obs/m (0.0031%–0.6234% obs/ft)
Fire 0.015%–20.00% obs/m (0.0046%–6.25% obs/ft)*

*Limited to 4% obs/ft for UL

Operating Conditions

Ambient

0°C to 39°C (32°F to 103°F)

Tested

-10°C to 55°C (14°F to 131°F)

Sampled Air

-20°C to 60°C (-4°F to 140°F)

Humidity

10% to 95% RH, non-condensing

Storage Conditions (non-operational)

Humidity

Dry (<95%)

Temperature

0°C to 85°C (32°F to 185°F)
Must not be exposed to sunlight or other radiation sources

Sampling Network

Maximum area of coverage:

Code Compliant

800 m² (8000 sq.ft)

Maximum (120sec transport time)

2,370 m² (25,500 sq.ft)
Local code requirements shall take precedence

Pipe

Internal Diameter

15 mm–21 mm (9 /16”–7 /8”)

External Diameter

25 mm (1”)

Maximum Pipe Lengths

1 x 80 m (260 ft), 2 x 50 m (164 ft)

Part Codes

VESDA VLC – VESDAnet

VLC-505

VESDA VLC – Relays Only

VLC-500

VESDA VLC - Apollo XP95

VLC-400

Remote Display (relays)

VRT-J00

Remote Display (no relays)

VRT-K00

Remote Relays (no display)

VRT-500

Downloads

Datasheets