Xtralis ICAM ILS-2 Aspirating Smoke Detector

Key Features
EN54-20 approved
Economical, single or dual area aspirated 'fire' detection
1 or 2 sampling pipes - each up to 100m in length
Coverage up to 1,500m2 at class C
3 users configurable alarm levels per channel

Overview

The XTRALIS ICAM ILS-2 Aspirating Smoke Detector provides laser air-sampling smoke detection to meet the individual requirements of many industrial and commercial applications. ICAM ILS-2 detectors are suitable for both medium sensitivity and multi-hole Class C applications.

These detectors are compact, rugged, waterproof and extremely versatile making them suitable for both general coverage and localised protection of equipment cabinets or ductwork.

The ICAM ILS-2 system has two inlet pipes and can be configured with dual addressable areas.

Each detector has two sets of alarm contacts per channel which are programmable across the dynamic sensitivity range of 0.06 to 3.33% per meter in 9 stages. The detectors internal fan is powerful and quiet and can support pipe lengths of up to 100m per channel.

How It Works

ICAM ILS Aspirating Smoke Detectors actively draw air via sampling a network of pipes. The air is filtered before being analysed by medium sensitivity laser spot (point) detectors that are incorporated into the system. Alert, Action or Fire alarm states are communicated through dry contact relays and indicated via LEDs on the detector's display.

ILS detectors employ a powerful, high-performance aspirator and sophisticated, software configurable, flow monitoring circuitry. The system features a ten element bar graph display that can be adjusted for low and high flow thresholds. Flow failure is reported as a device fault via dedicated fault relays.

Programming and Diagnostics

ICAM ILS-2 Detectors have three alarm levels. The sensitivity threshold for each alarm level, along with fan speed and flow sensitivity, can be individually programmed. ILS-2 detectors can be configured using a PC via its USB interface or can be figured locally using an integrated programing interface.

Additional Features

  • Integral Display and Programmer
  • Field serviceable and/or replaceable laser detection element
  • Easy to install, commission and maintain
  • Low operating current
  • Rugged IP65 enclosure
  • Single, redundant or coincidence detection strategies

Approvals

EN54-20
CE
VdS
CPD

Tech Specs

Mechanical

Sampling Pipe Inlets

1 or 2 (EF-LASD1 & EF-LASD2 respectively)

Detectors

1 or 2, 0.06%/m Laser Point Detectors (fitted)

Sampling Holes (Max)

18 Class C, 6 Class B, 3 Class A

Sampling Pipe Length

100m (max) per pipe. For VdS approved installations, consult manual

Sampling Pipe Diameter

1 or 2 x 25mm or 3/4” (27mm) nominal bore

Exhaust Air Pipe Outlet

1 (25mm or 3/4”)

Electrical

Supply Voltage

Nominal 24Vdc (18 to 30Vdc)

Operating Current

350mA max (fan speed dependant)

Sensitivity

0.06 - 3.33% obscuration per metre, adjustable in 9 stages

Alarm Levels

Programmable Alert, Fire 1, Fire 2 (per channel)

Operating Modes

Single detector, redundancy, double-knock

Settings

Isolate, latching, non-latching, operating mode, reset

Programming/set-up

Integral control switch’s and/or PC via USB

Event Log

1000 Events

Fault Monitoring

Power failure (common), flow fault per channel, detector fault

Relay Outputs

2 alarm & 1 fault per channel (changeover contacts)

Cable Terminals

Removable 2.0mm maximum

Display

5 common status plus 10 segment LED bargraph per channel

User Controls

External weatherproof membrane - Code protected

Flow Monitoring

Thermal, with adjustable high/low and sensitivity limits

Environmental

Operating Temperature

-10 to +50°C

Operating Humidity

10 to 95% (non condensing)

IP Rating

IP65 with exhaust pipe fitted and cable entries sealed

General

Filtration (Standard Internal)

Replaceable dust particle. Harsh environment filter also available

Filtration (External)

Optional, external harsh environment filter

Housing Material

ABS with tamper-proof locking mechanism

Mounting

Upright, horizontal or inverted

Weight

2.7kg

Dimensions (W x H x D)

259 x 184 x 166mm

Part Codes

ILS-2 Laser Air-sampling Smoke Detector with 2 inlets