Xtralis ICAM IAS Aspirating Smoke Detector

Key Features
Single or dual channel fire detection
Uses analogue addressable or conventional detectors (not supplied)
Multiple configuration options
Multiple detection strategies
Highest fan capacity in its class

£384.00

(Exc. VAT: £320.00)

Part Number: IAS-1

Overview

ICAM IAS is a flexible aspirating smoke detector from Xtralis. The ICAM IAS is well suited for a range of applications. The ICAM IAS provides fast and reliable detection that can be integrated with any existing fire alarm control panel - helping to maintain aesthetics of a property, provide a tamper proof detection solution or simply replace traditional point detectors.

The ICAM IAS combines standard field-serviceable detectors with a stand alone air-sampling solution.  ICAM IAS detectors actively draw air from the protected area, through sampling holes in a network of pipe, to its detection chamber. The sampled air is then analysed by conventional or analogue point detectors that are installed within the chamber.

The IAS is available with one inlet pipe (IAS-1) or two inlet pipes (IAS-2) and is compatible with a range of detector technology types including photoelectric, ionisation, heat,  carbon monoxide and more.

The ICAM IAS is a cost effective and simple to install and configure aspirating smoke detection solution. On top of this, in applications where an existing fire detection system is already in place, the ICAM IAS systems can be easily integrated with the existing fire alarm control panel.

Detection Strategies

ICAM IAS systems can be configured for single or dual addressable area detection, redundant detection, multi-criteria detection, coincident or double-knock detection and more.

Additional Features

IP65 enclosure
Up to 50m (328 ft) per sampling pipe
Microprocessor controlled
Integral display and programmer
Field serviceable air filter
Adjustable aspirator speed with airflow monitoring

Applications

Xtralis ICAM IAS detectors befit almost any application and particularly excel in:

Commercial spaces such as lift (elevator) shafts, air conditioning or extraction ducts or other inaccessible areas
Locked or security controlled areas such as prison cells
Wet and/or dusty environments
Floor and ceiling voids
Food preparation, pharmaceutical, cleaning and other hose-down areas

Approvals

EN54-20 (VdS) (Sensitivity Class dependant upon point detector used)
CE EMC
CPD
ActivFire

Tech Specs

Mechanical

Detectors

  • 1 or 2 analog addressable or conventional spot (point) detectors
  • A variety of detector technology types (photoelectric, ionization, heat, CO etc.)
  • Spot (point) detectors with universal screw mounting

Inlet Pipe Size

  • Outer Diameter: 25 mm (0.98 in.)
  • Inner Diameter: 21 mm (0.83 in.)

Sampling Network

  • Pipe Length: Up to 50 m (328 ft) per inlet
  • Pipe length may vary subject to specifications by local codes and standards, please refer to your regional IAS product guide for further detail

Electrical

Supply Voltage

  • 24 VDC nominal (18 to 30 VDC)
  • Note that spot (point) detectors are powered from the fire alarm field wiring

Operating Current

  • 300mA max (fan speed dependant)

Relay Outputs

  • IAS-1 - 1 fault relay
  • IAS-2 - 2 fault relays

Flow Monitoring and reporting

High and Low adjustable Fan:
  • Control: 10 programmable speeds
  • Pressure: 250 Pa

Environmental

Operating Conditions

  • Temperature: -10 to 60 °C (14 to 140 °F)
  • Humidity: 10 to 95% RH (noncondensing)

IP Rating

  • IP65

General

Filtration

  • Serviceable filter
  • External filter optional

Dimensions (WHD)

  • 259 mm x 184 mm x 166 mm (10.2 in. x 7.2 in. x 6.5 in.)

Part Codes

Aspirating Smoke Detectors

IAS-1 Air-sampling Smoke Detector with 1 Inlet
IAS-2 Air-sampling Smoke Detector with 2 Inlets

Baffles

06-ZE10 Baffle for Zeta FEO2000, FEAO2000 (10 Pack)
06-AP10 Baffle for Apollo S65, XP95, Discovery (10 Pack)
06-AP20 Baffle for Apollo Multisensor (10 Pack)
06-HK10 Baffle for Hochiki SLR-E3, ALG-E (10 Pack)
06-SS10 Baffle for System Sensor 2251EM,7251, LZR1-M, FSL751, SDX751 (10 Pack)
06-AD10 Baffle for ADT 801PH MX (10 Pack)
06-GT10 Baffle for Gent S-Quad (10 Pack)
06-NT10 Baffle for Nittan EV-P (10 Pack)
06-0000 Blanking Baffle (10 Pack)

Filters

02-FL53 Replacement Filter Element, Coarse 20ppi (Pack of 10)
02-FL56 Replacement Filter Element, Fine 44ppi (Pack of 10)

Power Supplies

28-001 2A Power Supply, 24VDC, 96-264VAC (EN54-4) 12AH Max
28-002 5A Power Supply, 24VDC, 96-264VAC (EN54-4) 17AH Max

Accessories

20-LA0015-03 Key for IAS/ILS

Downloads

Datasheets

Manual and certification on request.

Contact Us