ProFyre Conventional Smoke & Heat Detectors

Key Features
Low Profile
360 Degree LED Indication
Lockable to base to stop unauthorised removal
Remote LED Output

Overview

ProFyre Addressable Detectors

The conventional range comprises of an optical smoke detector, rate of rise heat detector (A2R), fixed heat detector (A2S) and a combined smoke and heat detector.


Tick Icon

ProFyre Compatible Addressable Panels

ProFyre Conventional Fire Alarm Control Panels

The ProFyre conventional detector range has been designed to complement the ProFyre C8 and C24 conventional control panels.


360 Icon

360 Degree Indication

The range has been housed in a stylish and attractive moulding with 360 degree LED indication.


Types Icon

ProFyre Conventional Detector Types

ProFyre Conventional Optical Detector

ProFyre Analogue Addressable Optical Detector

The optical smoke detector uses a pulsing IR LED and photodiode to detect IR scatter caused by smoke entering the chamber. The detector is particularly suitable for detecting optically dense smoke, involving materials such as soft furnishings, PVC, plastic, foam and all similar materials which produce small visible particles (0.5 to 10μm).

Approval Label


ProFyre Conventional A2R Heat Detector (Rate of Rise)

The rate of rise heat detectors use a thermistor arrangement to sense a quick rise in temperature and also a fixed threshold temperature of 57°C.

ProFyre Analogue Addressable A2R Heat Detector

Approval Label


ProFyre Conventional A2S Detector (Fixed Heat)

ProFyre Analogue Addressable A2S Detector

The fixed heat detector has a single thermistor arrangement that initiates an alarm at a temperature of 90°C.

Approval Label


ProFyre Conventional Combined Smoke & Heat Detector

The combined smoke and heat detector uses a combination of features from the optical smoke detector and heat detector.

ProFyre Analogue Addressable Combined Optical Smoke & Heat Detector

Approval Label

Tech Specs

Detector Class

Optical Smoke

Rate of Rise & Fixed Heat (A2R)

Fixed Heat (A2S)

Combined Smoke & Heat

Alarm Condition

Optical Smoke: 2.4% obs/m

Rate of Rise & Fixed Heat (A2R): 57°C

Fixed Heat (A2S): 90°C

Combined Smoke & Heat: 2.4% obs/m

Coverage

Optical Smoke: 100m²

Rate of Rise & Fixed Heat (A2R): 50m²

Fixed Heat (A2S): 50m²

Combined Smoke & Heat: 100m²

Operating Voltage

10.50 to 33Vdc

Quiescent Current

40μA

Alarm Current

35mA

Operating Conditions

Tested to: -10°C to +50°C (14°F to 122°F)
Maximum Continuous Temperature: 0°C (32°F)
Humidity: 0% to 95% RH, non-condensing

IP Rating

IP43

Design Environment

Indoor Use Only

Weight

0.075kg (0.16lbs)

Ordering Information

12-020 ProFyre Conventional Optical Smoke Detector
12-021 ProFyre Conventional A2R Rate of Rise Heat Detector
12-022 ProFyre Conventional A2S Fixed Heat Detector
12-023 ProFyre Conventional Combined Smoke & Heat Detector