ProFyre C24 Conventional Fire Alarm Panel

Key Features
Approved to EN54-2 & 4
8, 16, 24 zone versions
4 monitored sounder circuits
Expansion of zone and sounder circuits
Repeater panel output

Overview

ProFyre C24 Conventional Control Panel

A flexible, fully-featured expandable modular based conventional fire alarm control panel available in 8, 16 or 24 zone versions. The panel provides a high standard of quality and reliability that is easy to install, commission, maintain and simple to operate.

The metal enclosure can be surface or semi-flush mounted and provides excellent access during the installation and commissioning stages. 4 monitored sounder circuits and a SELV fault and fire relay are included with further expansion options for zones and sounder circuits using the modular based expansion PCB cards.


Tick Icon

ProFyre Conventional Devices

ProFyre Conventional Devices

Complemented by a complete range of ProFyre conventional field devices, the ProFyre C24 is the logical choice for systems that require clear alarm management and ease of use.


Wiring Icon

Typical Wiring Diagram

ProFyre C24 Typical Wiring Diagram


Mounting Icon

Mounting Options

The ProFyre C24 has been designed to accommodate for many applications. Available in 2 versions; surface or semi-flush.

ProFyre C24 Mounting Options


Approvals

The ProFyre C24 is fully approved by Intertek for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).

  • EN54-2:1997+A1:2006
    Fire detection and fire alarm systems - Control and indicating equipment.
  • EN54-4:1997+A1:2002+A2:2006
    Fire detection and fire alarm systems - Power supply equipment.

ProFyre C24 Approvals


Tech Specs

Dimensions

ProFyre C24 Dimensions

Detection

Zones

8, 16, 24

Device

32 per Zone

Zone Voltage

21Vdc Nominal

Zone Short Circuit Protection

100mA

Zone End of Line Device

1N4002 Diode

Manual Call Point Trigger Resistance

470Ohm or 680Ohm

Technology

Panel

Sounder Delay

One Man Test Facility

Zonal & Sounder Isolation

Hardware

Indication

Power, Common Fire, Common Fault, Supply Fault, Earth Fault, System Fault, General S/C, Sounder Fault Disablement, Sounder Delay, F.A.R.E Active, F.A.R.E Fault Disablement, Repeater Fault, General Disablement, General Test, Controls Active, Zone 1-24 Fire, Zone 1-24, Fault, Zone 1-24 Test/Disabled

Controls

Panel Access, Start/Stop Sounders, Silence Buzzers, Reset, LED Test, Sounder Delay, Function, Scroll, Select

Outputs

1 x VFCO Fault Relay: SELV @ 1A

1 x VFCO Fire Relay: SELV @ 1A

1 x Auxiliary Output: 24Vdc @ 250mA

Inputs

Sounder Alarm Outputs: 4 x 150mA @ 24Vdc

Sounder Circuit

Sounder Activation Delay: 0 to 9 Minutes - In 1 Min Increments

Sounder End of Line Device: 10K Resistor

Electrical

Mains Voltage

230Vac +/- 10% @ 50/60Hz

System Voltage

28Vdc Nominal (19 - 32V)

Charger Voltage

27.6V @ 25°C (No Batteries Connected)

Total PSU Output

5A

Battery Capacity

2 x 12V 17Ah SLA (Max)

Battery Cut-off Voltage

Less Than 20.5Vdc

Mechanical

Dimensions W x H x D

485mm x 477.5mm x 125mm (19.09in x 18.80in x 4.92in)

Cable Entries

Top: 20 x 20mm Knockouts

Bottom: 6 x 20mm Knockouts

Mounting Points

3

Material

Mild Steel

Colour

RAL 7035

Environmental

Operating Conditions

Operating Temperature: 0° to +50°C (32°F to 122°F)

Humidity: 0% to 95% RH, non-condensing

IP Rating

IP30

Design Environment

Indoor Use Only

Ordering Information

13-010 ProFyre C24 8 Zone Conventional Fire Alarm Panel
13-011 ProFyre C24 16 Zone Conventional Fire Alarm Panel
13-012 ProFyre C24 24 Zone Conventional Fire Alarm Panel
40-004 Semi-flush Mount Bezel for ProFyre A4 & ProFyre C24
13-014 ProFyre C24 8 Zone Expansion PCB
13-015 ProFyre C24 8 Zonal Sounder Expansion PCB

Contact Us