ProFyre Analogue Addressable Zone Monitor

Key Features
Loop powered
Addressed with dip switches or a hand-held programmer
Integral bi-directional short circuit isolator
Visible status, fault and alarm LED indication
Surface or Semi-flush mounting

Overview

The Addressable Zone Monitor enables compatible conventional trigger devices to be connected to the addressable loop, forming as a single radial wired zone circuit.

The interface module is loop powered and there can be a maximum of 16 devices per ProFyre loop, subject to other device loading.

A bi-directional short-circuit isolator has been fitted to the interface module to ensure continued funtionality in the event of a short-circuit on either the loop in or out terminals.

The interface is supplied with a back box incorporating four 20mm knock-outs and three mini trunking knock-outs for surface mounting purposes. The device is also compact enough to be mounted directly on to a double European back box for semi-flush mounting. To minimise any damage during installation, all electronics are protected by a cover. The ProFyre Addressable Zone module has an ingress protection rating of IP21C (with back box) for internal use only.

The ProFyre Addressable Zone Monitor is compatible with the analogue addressable ProFyre A4, A2 and T8 2-wire fire alarm systems.

Approvals

Intertek

CPR

0359-CPR-00472

Tech Specs

Type

Addressable Zone Monitor

Operating Voltage (Loop)

17 to 28Vdc

Quiescent Current

3.5mA

Alarm Current (LED OFF)

12.6mA

Alarm Current (LED ON)

13.2mA

Isolating Current

7.3mA

Input End Of Line

6.2k

Nominal Alarm Triggering Resistor

1k

Operating Conditions

Tested to: -10°C to +55°C (14°F to 131°F)

Humidity: 0% to 95% RH, non-condensing

IP Rating

IP21C

Design Environment

Indoor Use Only

Weight

0.22kg

Part Codes